Canadian Products

Display:

Type RW90 copper conductors are suitable for use in conduit and raceways installed underground in conduits, in wet locations, and where condensation and moisture accumulations within the conduit do not exceed 90oC. When used as RHH or RHW-2, conductor temperatures shall not exceed 90oC in wet or dry locations. Voltage rating for RW90 conductors is 600 volts. Insulation rated for use to -40oC (UL).

RWU90 copper conductors are suitable for use in conduit and raceways installed underground in conduit, in wet locations, and where condensation and moisture accumulations within the conduit do not exceed 90o. Conductor temperatures shall not exceed 90oC in wet or dry locations. Voltage rating for RWU90 conductors are 1000 volts. Insulation rated for use to -40oC.

Type T90 building wire is intended for general purpose applications and may be installed in conduit, duct, or other recognized raceways in wet (60oC oil/90oC water) or dry (105oC) locations. For both new work and rewiring applications, the smaller diameter of wire permits additional circuits or larger conductors to be installed in the conduit without exceeding maximum fill limitations. The insulation is a high quality, heat and moisture resistant polyvinyl chloride compound over which a heat and light stabilized nylon jacket is tightly applied.